Unitemp Blog

15.12.2015

This is usually an indication that the sensor signal is out of the configured range. Check that the input range is within tolerance:

  1. Press and hold the button until is displayed;
  2. Press...
15.12.2015

This usually an indication of a) a faulty Pt100 or analogue signal or b) wrong sensor type or c) sensor signal is out of range or d) incorrect/damaged input connection.

Solution

  1. Step 1: Check the jumper setting

    VT = transmitter supply for 2 wire analogue signal
  2. Step 2: If input type is known (Pt100,...
14.12.2015

This is usually an indication of a faulty thermocouple temperature sensor (open circuit or faulty cable).

Solution:

Step 1: If input type is known (eg. Thermocouple type J), change tyP parameter.
  1. Press and hold the Fbutton until is displayed;
  2. ...
19.03.2015

Thermon polymer insulated heat tracers have an overjacket covering the braid. This overjacket is intended be a chemical corrosion barrier for the braid and also provide additional mechanical strength.

For what chemicals do -OJ and -FOJ overjackets offer protection?

In general for Thermon BSX Self-Regulating Heatng Cables, the polyolefin...

19.03.2015

A heating cable that includes a continuous series of short, independent heating circuits. Localized damage can result in only partial loss of heating. Watt-per-unit length output is relatively unchanged by variations in circuit length up to several hundred feet. Known as “cut-to-length”, parallel cables are easy to size because circuit lengths (within limits) do not have to be considered.

19.03.2015

Any heating cable providing a watt output which increases as temperatures fall and decreases as temperatures rise. Self-regulating heating cables use a carbon matrix-heating element with variable resistance.

Self-regulating cables have a conductive polymer-heating element where the resistance exhibits a PTC characteristic, the resistance of the element increases with temperature. Conversely, the cable’s power output decreases with increasing temperature. As the temperature increases...

19.03.2015

Parallel resistance heating cables that will reduce their power output as temperatures rise but do not have the high in-rush currents associated with self-regulating heating cables.

These cables are capable of delivering high watt per foot heat outputs.

19.03.2015

Series resistance cables are single or multiple metal alloy conductors with a voltage applied at the ends.

The power output is a function of the voltage applied and the overall resistance based on type of metal alloy and circuit length. If the length changes the power output of the cable changes, so these heating cables are not considered “cut-to-length”.

19.03.2015

Both self-regulation and power-limiting cables exhibit a PTC (positive temperature coefficient) resistance characteristic and subsequently power output decreases with increasing temperature.

As self-regulating heating cables increase in temperature they eventually reach a “shut-off” temperature.

Power-limiting cables provide higher power output at higher temperatures; however, as temperature increases power-limiting cables do reach a “shut-off” temperature.

19.03.2015

Yes. Pipe support (non-insulated) and valves represent a region of much higher heat loss. This local higher heat loss must be made up with additional heating cable.