testo thermal imager
parallel trace heating
testo 350
displacement transducer
electric heat tracing
heat tracing
electrical heat tracing
Gefran indicators
emissons
series resistance cables
FAQs
maintenance
Gefran 600 controller
fluegas analysis
flue gas
technical services
compliance testing
trace heating
Home
displacement transducer

displacement transducer
Can displacement transducers be repaired?
Wiper replacement can be facilitated for certain potentiometers. Kindly contact for further details & request support.
My previous potentiometer had a resistor value of 10k - is it safe to use a displacement transducer with a 5kΩ resistor value?
Yes. A displacement transducer is a voltage divider (not a variable resistor) so resistive value is of little importance
unless the data acquisition system has specific requirements. Be careful however to observe the power supply
capabilities to define maximum absorbed current.
Displacement transducer: The potentiometer is not linear
Linearity is greatly influenced by the input impedance value - so this is vital for considered applications.
For example, whilst it is theoretically possible to connect a potentiometer to a , say 0-10Vdc, input of a PLC, the input impedance value of of the PLC must be considered.
Thank you for your enquiry below. Our heat tracing specialist will be in contact with you soon...
Good day. Please quote on heating wires for a freezer room (-30 deg.C)
Heating wires to...