The standard retransmission setting is 0-10V, but can be changed to 2-10V/ 0-20mA or 4-20mA.
Step:
S1 = ON (0 -10Vdc) Standard | S1 = ON (Jumper terminals bridged)
S1=OFF (0-20mA) | S1 = OFF (Jumper terminals open)
Change the jumper setting on the analogue output card to S1 = OFF
- Step: Calibrate the 0-20mA to 4-20mA
Connect a multimeter/ampmeter to output 3 of the controller (mA dc)
- Press and hold the
button until
appears;
- Using
buttons configure value to 99;
- Press the
key once,
appears;
- Using
buttons configure value to 128;
- Press the
key once,
appears
- Using
buttons configure value to 99;
- Press and hold the
key until
is displayed;
- Using
buttons configure value to 1;
- Press the
key once, C.L appears;
- Using the
keys, configure the value on the multimeter to 4mA;
Example: By keeping thekey pressed in, the current value displayed on the multimeter will increase.
- Press the
key once, C.H appears;
- Using the
keys, configure the value on the multimeter to 20mA;
- Press and hold the button to return to the main screen
- Press and hold the