Gefran controller: Can the analog output on a 600-x-x-C-x-x be converted from 0-10V to 2-10V?

Yes, although 0-10V is the standard output, the analogue signal can be changed to 2-10V.

  1. Press and hold the button until appears;
  2. Press the button repeatedly until appears;
  3. Using buttons configure value to 64 or 65;
  4. Press and hold the button to return to the main screen
     