Parallel Heating Cables
More Information
Self-Regulating-, Constant Watt-, Power-Limiting or Foundation Heating Cables
Parallel trace heating cable consists of two parallel conductors (phase, neutral) with a conducting material in between. The conducting material produces even heating power (Watts/m) over the entire length of the cable.
The advantage of parallel heating cables is that they can be cut to any length with the termination being at one end of the cable and is easy to terminate.
For safety reasons it is not recommended to exceed the design wattage.
If used in a more hazardous environment such as the chemical or petrochemical industry, the cables can be lagged with a unique, chemically resistant outer fluorpolymer jacket.
contact us to discuss your requirements.
Thermon
BSX:
Self-Regulating
Heating Cable
- Max operating temperature
Power ON: 65ºC - Max exposure temperature
Power OFF: 85ºC - Power options: 3 | 5 | 8 | 10
- W/m @ 10 ºC:
9 | 15 | 25 | 32 - Voltage Range: 100-277 Vac
- T-Rating: T6 | T5
*freeze protection *low process temperature maintenance
*no steam clean
Thermon
RSX15-2:
Self-Regulating
Heating Cable
- Max operating temperature
Power ON: 65ºC - Max exposure temperature
Power OFF: 85ºC - Power options: 15
- W/m @ 10 ºC: 48
- Voltage Range 100-277 Vac
- T-Rating: T5
*freeze protection *low process temperature maintenance *anti icing *no steam clean
Thermon RSX
Foundation Heating:
Self-Regulating
Heating Cable
- Frostheave protection of cryogenic storage vessels
- Heat output responds to surrounding conditions
- Operating Voltage:
230/240 VAC - Start-Up Temperature:
0-20°C - T-rating: T6 | T5
*foundation heating/ slab heating
Thermon
FP:
Constant Watt
Heating Cable
- Max operating temperature
Power ON: 65ºC - Max exposure temperature
Power OFF: 200ºC - W/m @ 10 ºC:
8 | 16 | 33 - Voltage Range:
120-240 Vac - T-Rating: T3 | T6
*freeze protection *low process temperature maintenance
*no steam clean
Thermon FP
Foundation Heating :
Constant Watt
Heating Cable
- Frost heave protection of cryogenic storage vessels
- Fibreglass overlay
- Nominal watt density:
16-33 W/m - Maximum Operating Voltage: 690 VAC
*frost heave protection *heating of cryogenic storage tanks * foundation heating
Thermon
KSX:
Self-Regulating
Heating Cable
- Max operating temperature
Power ON: 121ºC - Max exposure temperature
Power OFF: 121ºC - Power options: 15 | 20
- W/m @ 10 ºC: 48 | 64
- Voltage Range 100-277 Vac
- T-Rating: T3
*freeze protection *medium process temperature maintenance
*no steam clean
Thermon HTSX:
Self-Regulating
Heating Cable
- Max operating temperature
Power ON: 121ºC - Max exposure temperature
Intermittent
Power ON: 215ºC
Power OFF: 250ºC - Power options:
3 | 6 | 9 | 12 | 15 | 20 - W/m @ 10 ºC:
9 | 18 | 27 | 37 | 48 | 64 - Voltage Range 100-277 Vac
- T-Rating: T3 | T2
*freeze protection *medium process temperature maintenance
*steam clean/ purge
Thermon VSX:
Self-Regulating
Heating Cable
- Max operating temperature
Power ON: 150ºC - Max exposure temperature
Intermittent:
Power ON: 232ºC
Power OFF 250ºC - Power options:
5 | 10 | 15 | 20 - W/m @ 10 ºC:
15 | 32 | 48 | 64 - Voltage Range 100-277 Vac
- T-Rating: T2 |T2
*freeze protection *medium - high process temperature maintenance *steam clean/ purge
Thermon HPT:
Power Limiting
Heating Cable
- Max operating temperature
Power ON: 215ºC - Max exposure temperature
Power OFF: 260ºC - Power options:
5 | 10 | 15 | 20 - W/m @ 10 ºC:
15 | 30 | 45 | 60 - Nominal Supply Voltage
120/ 240 Vac - T-Rating: Stabilised design/ thermostat
*medium - high process temperature maintenance
*steam clean/ purge
Apart from the connections, some of these parallel electrical heating cables can be immersed into fluids.
What are Self-Regulating or Power Limiting Heating Cables?
Where resistance of the material increases as the operating temperature rises, a reduction of heating power occurs.
These are termed "self regulating" or power limiting trace heating cables.
Excellent for metallic or non-metallic piping and tanks, our self-regulating heating cables allow for ease of design & installation with applications ranging from freeze protection to process temperature maintenance to foundation heating.
High performance power-limiting heating cables are designed specifically for process temperature maintenance or freeze protection where high temperature maintenance or high temperature exposure is required.
What are Parallel Constant Watt Heat Tracing Cables?
Parallel constant watt heating cables include a continuous series of short, independent heating circuits. Power output is relatively unchanged by variations in circuit length up to several hundred metres.
These cables are designed specifically for freeze protection or process temperature maintenance of pipes, tanks and equipment.
Contact our consulting engineers Select Cables & Get a Quote